City SiteGuide | Search
Water Services
811 East Red Hills Parkway
St. George, UT 84770
(435) 627-4800

To report water and/or power problems please call (435) 703-1140.

Arsenic Information
Conservation
Waste Water Plant
Water Quality Report
History
Back Flow Program
Frequently Asked Questions & Answers
Drinking Water Plant
Kids Corner

Email the Water Department

Backflow Devices and Assemblies
Types of Backflow Preventions There are five distinct types of piping or mechanical assemblies which are considered to be backflow prevention assemblies; but, it must be stressed that these are not all equally acceptable as protection against all types of hazards. The degree of hazard must be assessed along with the type of cross-connection present to determine which type of backflow prevention assembly is most suitable to the situation.

Note: Testable backflow assemblies require to have a certified inspection and operational test at least once a year.

Air Gap

An Air Gap is a physical separation of the supply pipe by at least two pipe diameters (never less than one inch) vertically above the overflow rim of the receiving vessel. In this case line pressure is lost. Therefore, a booster pump is usually needed downstream, unless the flow of the water by gravity is sufficient for the water use. With an air gap there is no direct connection between the supply main and the equipment. An air gap may be used to protect against a contaminant or a pollutant, and will protect against both backsiphonage and back pressure. An air gap is the only acceptable means of protecting against lethal hazards.
Atmospheric (non-pressure) Type Vacuum Breaker {AVB} (Non Testable)

The AVB is always placed downstream from all shutoff valves. Its air inlet valve closes when the water flows in the normal direction. But, as water ceases to flow the air inlet valve opens, thus interrupting the possible backsiphonage effect. If piping or a hose is attached to this assembly and run to a point of higher elevation, the back pressure will keep the air inlet valve closed because of the pressure created by the elevation of water. Hence, it would not provide the intended protection. 1.This type of assembly must always be installed at least six (6) inches above all downstream piping and outlets. 2. This assembly may not have shutoff valves or obstructions downstream. A shutoff valve would keep the assembly under pressure and allow the air inlet valve (or float check) to seal against the air inlet port, thus causing the assembly to act as an elbow, not a backflow preventer. 3.The AVB may not be under continuous pressure for this same reason. An AVB must not be used for more than twelve (12) out of any twenty-four (24) hour period. It may be used to protect against either a pollutant or a contaminant, but may only be used to protect against a backsiphonage condition.

Pressure Vacuum Breaker {PVB}} (Testable)

The PVB includes a check valve which is designed to close with the aid of a spring when flow stops. It also has an air inlet valve which is designed to open when the internal pressure is one psi above atmospheric pressure so that no non-potable liquid may be siphoned back into the potable water system. Being spring loaded it does not rely upon gravity as does the atmospheric vacuum breaker. This assembly includes resilient seated shutoff valves and testcocks. The PVB is designed to operate under constant pressures for long periods of time.

1. The PVB must be installed at least twelve (12) inches above all downstream piping and the highest fixture flood level rim, outlet, or highest point of water use.

2. The PVB may be used to protect against a pollutant or contaminant, however, it may only be used to protect against backsiphonage. It is not acceptable protection against back pressure.

3. The PVB shall be installed in a vertical position with adequate space to facilitate maintenance and testing.

Double Check Valve Assembly {DC}(Testable)

The Double Check Valve Assembly consists of two internally loaded, independently operating check valves together with tightly closing resilient seated shutoff valves upstream and downstream of the check valves. Additionally, there are resilient seated testcocks for testing of the assembly. The DC may be used to protect against a pollutant only. However, this assembly is suitable for protection against either backsiphonage or back pressure.






Reduced Pressure Principle Assembly {RP}(Testable)

This assembly consists of two internally loaded independently operating check valves and a mechanically independent, hydraulically dependent relief valve located between the check valves. This relief valve is designed to maintain a zone of reduced pressure between the two check valves at all times. The RP also contains tightly closing, resilient seated shutoff valves upstream and downstream of the check valves along with resilient seated testcocks. This assembly is used for the protection of the potable water supply from either pollutants or contaminants and may be used to protect against either backsiphonage or back pressure.

1. This assembly shall not be installed in a pit below ground level. Semiburied pits are acceptable if the RP is installed above the ground or the maximum flood level with an approved air gap between the relief valve port and the daylight drain.

2. The relief valve port shall not be submerged in groundwater. That would create a cross connection is that may be more serious than the hazard that the assembly isolates.




Customer Service Survey